9. REFRIGERANT PIPING
A) Maximum Pipe Length and Maximum Number of Bends
Always choose the shortest path for refrigerant piping and follow the recommendation as tabulated below:
Remarks: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.62m/25ft.
B) Flare Connection
Cut the pipe stages by stages, advancing the blade of pipe cutter slowly.
Remove burr with the burr remover. Hold the flaring end down to prevent burrs from dropping inside
pipe.
Model M5WMX010GR M5WMX015GR M5WMX020GR M5WMX025GR
Maximum length, L (m/ft) 15/49 15/49 30/98 30/98
Max. elevation, H (m/ft) 5/16.4 5/16.4 8/26.2 8/26.2
Max. number of 90° bends 10 10 10 10
Liquid pipe size ¼” ¼” ¼” ¼”
Gas pipe size
3
/
8
½” ½”
5
/
8