©2004 McQuay International +1 (800) 432-1342 www.mcquay.comISO 9002REGISTEREDMWMX - 2005DC Inverter Wall MountedModels: MWMX 010FR MWMX 015FR
8Model : MWMX 010FR / 015FR - M5LCX 010CR / 015CRRefrigeration Cycle Diagram
9Model : MWMX 010FR / 015FRModel : M5LCX 010CR / 015CRWiring Diagrams
10Remote Controller Operation GuideG7 Remote ControllerTransmission source• The source where the signal willbe transmitted1Temperature setting• To set
INDICATOR LIGHTSIR signal receiverWhen all infrared remote control operating signalhas been transmitted, the signal receiver onindoor unit will make a
12Inverter Heatpump Unit LED Indicator Lights For Inverter Heatpump UnitCool / Dry Stand-by / FanTimerHeatLED DisplayThe LED in indoor and outdoor uni
13Blink Fault Indication Corrective Action1 Outdoor ambient sensor error Check ambient sensor wire and connection2 Outdoor coil sensor error Check coi
Before Operating, Please Read The Following “Safety Precautions” Carefully.To prevent injury to the user or other people and properties damage, the fo
15CautionPlease confirm the following important points when installation• Grounding is necessaryIt may cause electrical shock if grounding is not perf
16SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R410A UNIT1) WHAT IS NEW REFRIGERANT R410A?R410A is a new HFC refrigerant which does not damage th
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is toensure that only the original composition of R4
Note : Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and
18Installation DiagramIndoor UnitOutdoor UnitCAUTION : Before installing the unit, ensure that the power supply matches the power requirement of the a
1) Selection Of Location And Space(A) Indoor UnitInstall the fan coil (indoor) unit at a location with the following requirements• Location is suitab
(B) Outdoor UnitAs condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximumcooling capacity
212) Drilling Holes And Mounting Installation PlateCAUTION:i) Please check the unit weight for each model. Always ensure that the wall is sufficiently
3) Indoor Unit Preparation• The refrigerant piping can be routed to the unit in 5direction, by using the cut outs in the unit casing.(See fig. 1)• Car
235) Water Drainage PipingThe indoor drain pipe must be downward gradient for smooth drainage. Avoid situation as shown in figurebelow.6) WiringElectr
7) Refrigerant PipingMaximum Pipe Length And Maximum Number Of BendsAlways choose the shortest path for refrigerant piping and follow the recommendati
254) After evacuation, unscrew the spindle (diagram B) for the gas to run to indoor unit.Additional ChargeThe refrigerant gas is charged in the outdoo
The unit is designed to give a long life operation with minimum maintenance required. However, it should be regularlychecked and the following items s
Pre Start Up Maintenance(After Extended Shutdown)– Inspect thoroughly and clean indoor and outdoor units.– Clean or replace air filters.– Clean conden
• Energy SavingTotal energy saved can be as high as 30% compared to the conventionally controlled units.• EfficientMcQuay DC Inverter series achieve e
28By means of pressure readings :By means of diagnosis flow chartGenerally, there are two kinds of troubles, i.e. starting failure and insufficient co
29The most common causes of air conditioner failure to “start” are :a) Voltage not within +/- 10% of rated voltage.b) Power supply interrupted.c) Con
30Model : MWMX 010FR / 015FRPPPPParararararts Listts Listts Listts Listts List1 Assy, Mounting Plate A50013032957 10 Fan Bush C/Flow Fan Black A110140
31Model : M5LCX 010 / 015CR1 ASSY,PAN BASE SL10/15C A50014057190 ASSY. CONTROL BOXASSY,CONDENSER COIL 5SL10/15C/10CR M5LCX 010CR A50044061024M5LCX 010
©2005 McQuay International +1 (800) 432-1342 www.mcquay.com
2MWMX 010 F RModel NameWM : Wall MountedSystemX : DC InverterBrandM : McQuayCapacity010 : 10,000 Btu/hSeriesF : F seriesModel TypeR : heatpumpOmitted
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDIT
Ensure the operating temperature is in allowable range.Cooling onlyHeatpump4 Caution :The use of your air conditioneroutside the range of working
Speed Overall Noise(RPM) 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz A (dBA) CriteriaH (1250)323335343123163833M (1110) 32 29 32 31 27 18 14 35 30L (
Measured in anechoic room at 1m front and 0.8m below the vertical centre line of the unitMeasured in anechoic room at 1m front and 0.8m below the vert
7Indoor UnitModel : MWMX 010FR / 015FROutdoor UnitModel : M5LCX 010CR / 015CRNote : Dimension in mmNote : Dimension in mmOutlines And Dimensions