18
M5MSX-2009
Application Information
Piping Connection To The Units
The outdoor unit is equipped with two to four sets of are joints depending on O/D unit model. Refer to table
below for are joint size and location.
In the case where gas pipe from the indoor unit does not match the outdoor are joints, two different are
joint connectors are provided. The connector should be connected as shown in gure.
No Flarte Joint Connector
1 3/7” to 1/2” Connector
2 1/2” to 3/8” Connector
Pipe Size mm/(in) Torque Nm/(ft - Ib)
6.35 (1/4) 18 (13.3)
9.53 (3/8) 42 (31.0)
12.70 (1/2) 55 (40.6)
Align the center of the piping and tighten the are nut sufciently with ngers.