©2008 McQuay International
12
Cassette indoor units
Model
MCK011UP
MCK015UP
MCK018UP
MCK020UP
MCK028TP
MCK032TP
MCK035TP
MCK045TP
MCK050TP
MCK060TP
W 2800 3600 4500 5600 7100 8000 9000 11200 12500 14000 Cooling
capacity
Btu/h 9560 12300 15370 19130 24250 27320 30740 38250 42690 47810
W 3200 4000 5000 6300 8000 9000 10000 12500 14000 16000 Heating
capacity
Btu/h 10930 13660 17080 21520 27320 30740 34150 42690 47810 54640
Power
220-240V~/50Hz
Sound level dB(A) 44 44 45 45 42 45 45 46 48 50
W×D×H(mm) 570×570×250 930×930×363
kg 22+2 22+2 23+2 23+2 37.5+5 39.5+5 39.5+5 39.5+5 39.5+5 39.5+5 Weight
(Unit+Panel)
lb 48+4 48+4 51+4 51+4 83+11 87+11 87+11 87+11 87+11 87+11
Power consumption (W)
56 56 60 60 72 84 110 125 140 155
Current(A) 0.25 0.25 0.27 0.27 0.33 0.38 0.50 0.57 0.64 0.70
Number of fan 1
H :m³/h 697 697 697 697 1200 1300 1300 1530 1650 1800
Air flow
H :CFM
410 410 410 410 706 765 765 901 971 1059
Drain Φ(mm)
20.5
Protection Anti-freezing , overheat
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in))
6.35(1/4”) 9.52(3/8”)
Gas Φ(mm(in))
9.52(3/8”)
12.7(1/2”) 15.88(5/8”)
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃.
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃.
3. Testing power supply: 220V~/50Hz.
Wall Mounted indoor units
Model MWM009TP MWM011TP MWM015TP MWM020TP MWM028TP
W 2200 2800 3600 5600 7100 Cooling
capacity
Btu/h 7510 9560 12300 19130 24250
W 2500 3200 4000 6300 8000 Heating
capacity
Btu/h 8540 10930 13660 21520 27320
Power
220-240V~/50Hz
Sound level dB(A) 39 39 42 44 49
W×D×H(mm) 799×198×260 899×198×260 1062×222×304
kg 10 12 16
Weight
lb 22 26 35
Power consumption (W)
24 36 40 48 68
Current(A) 0.11 0.16 0.18 0.20 0.31
Number of fan 1
H :m³/h 460 510 590 860 1100
Air flow
H :CFM 271 300 347 506 647
Drain Φ(mm)
16.5 20.5
Protection Anti-freezing, overload
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in))
6.35(1/4”) 9.52(3/8”)
Gas Φ(mm(in))
9.52(3/8”) 12.7(1/2”) 15.88(5/8”)
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃.
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃.
3. Testing power supply: 220V~/50Hz.
Komentarze do niniejszej Instrukcji