McQuay MLCV Dokumentacja Strona 129

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 144
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 128
By Means Of Diagnostic Flow Chart :
Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling/heating. “Starting failure”
is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insufficient
cooling / heating”.
i) Diagnosis of Electric Circuit
127
The most common causes of air conditioner failure to “start” are :
a) Voltage not within ±10% of rated voltage.
b) Power supply interrupted.
c) Improper control settings.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.
Przeglądanie stron 128
1 2 ... 124 125 126 127 128 129 130 131 132 133 134 ... 143 144

Komentarze do niniejszej Instrukcji

Brak uwag