Installation In Zone Exposed To Strong Wind Or High Snow Falls (For Heatpump Model)
Installation Clearance
Single Condensing Unit Installation
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to
smooth air flow. Select the coolest possible place where intake air should not be hotter than the outside
temperature (max. 45°C)
NOTE :- (1) If any obstacle is higher than 2 m, or if there is any obstruction at the upper part of the unit, allow
more space than indicated in the table above.
All Models A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm