M. CHILLED WATER FAN COIL SERIES
Model Board Handset
CK 20 - 50 AW W1V2 G6 Wireless Controller or
CE 20 - 50 DW W1V3 Netware-1 Wired Controller
CC 10 - 60 CW
Self Diagnosis Table
Wireless Wired Operation / Faulty Indication
Power LED Other LEDs 7 Segment Display
Blinks 4 times Fan blinks E1 Blinking Room sensor Contact loose / short
Blinks 4 times Sleep blinks E2 Blinking Indoor coil sensor contact loose / short
Blinks 1 time Cool blinks E4 Blinking Pipe water temperature fault
Blinks 2 times Cool & Fan blink E6 Blinking Pump faulty
N. ROOFTOP PACKAGED AIR CONDITIONER
Model Board Handset
A) RT 80/100/150/200 MECHANICAL PAC-204RC
Self Diagnosis Table
7 Segment Display Operation / Faulty Indication
E01 Blinking Thermistor Open Circuit
E02 Blinking Thermistor Open Short
E03 Blinking External Switch Is Closed
B) RT 150/250/300 SQCH SQ-LCD
Self Diagnosis Table
Please refer to Page 34
C) RT 60/80/100/120 U1SB125 SLM-3
Self Diagnosis Table
Please refer to Page 33
Mainboard: W1V3
Wireless Wired Operation / Faulty Indication
Power LED Other LEDs 7 Segment Display
Blinks 4 times Fan blinks E1 blinking Room sensor contact loose/short
Blinks 4 times Sleep blinks E2 blinking Indoor coil sensor contact loose/short
Blinks 3 times Cool & dry blink E4 blinking Pipe water temperature poor
Blinks 1 times Cool blinks E5 blinking Pipe water temperature fault
Blinks 2 times Cool & fan blink E6 blinking Pump faulty
37 38
Mainboard : W1V2
Przeglądanie stron 38