C) W1V3 - Chilled Water Fan Coil Unit
The Standard Board (W1V3) comes with a VALVE jumper. The system can be
configured as the jumper selection listed below:
VALVE Jumper HEAT Jumper
Heatpump Mode & Valve Application
Heatpump Mode & Valveless Application
Cooling Mode & Valve Application
Cooling Mode & Valveless Application
: Jumper Remained : Jumper Removed
VALVE & HEAT Jumper Location
Model: WM 05-25FW
1. VALVE jumper is plugged into JVLV connector on the emergency switchboard.
2. Heat jumper is plugged into JMODE connector on the emergency switchboard.
Model: CK 20-50AW, CK 15-30BW, CE 20-50DW and CC 10-60CW
1. VALVE jumper is plugged into JVLV connector on the main board.
2. HEAT jumper is plugged into OD connector on the main board.