I) Auto Random Restart Selection
Auto restart at the last state memory setting:
• Shorted at JH/JP1 jumper at main board for auto restart (supplied);
• Remove the jumper to have non-auto restart.
WM-F Series WM-FR Series Other Model
(D1.7 Board) (U1.3 Board) (U1.4 Board)
II) Hot Keep Selection
Three selection available:
a. Fan stop if indoor coil temperature < 30°C (OFF);
b. Fan runs at low speed if indoor coil temperature < 30°C and stop if indoor coil
temperature < 18°C (ON);
c. Cycle of low fan running for 30 seconds and fan off for 120 seconds and repeat
(INTERVAL).
WM-F/FR (U1.3 Board)
3 selection available at the slide switch on the On/Off Switch board; Preset at OFF.
Other models (U1.4 Board)
At CN3 location on the PCB,
i. Remove the connector to have (b)-Fan ON and
ii. Cut off the big resistor (12k Ohm) to have (c)-Fan INTERVAL
Non-ducted Model - Standard setting is (a)-Fan OFF
Ducted Model - Standard setting is (c)-Fan INTERVAL