D) Netware-1 Controller
Feature : Dip Switch Setting for Model Selection
Pin Function Remarks Model
JH & JD COOL, DRY, FAN JH - OFF; JD - ON Cooling only
COOL, DRY, FAN, HEAT JH - ON; JD - ON Heatpump
RTC No real time clock RTC-OFF
Real time clock RTC-ON
NO DRY With Dry function NO DRY - ON
Dry function NO DRY - OFF
E) Air Cooled Mini Chiller
Entering Water Temperature
Mode Factory Setting
COOL 12°C
HEAT 40°C
SW2 Factory Setting (for COOL mode)
Set Temp. SW2
°C SW2-3 SW2-2 SW2-1
Set by VR3 0 0 0
3 001
4 010
5 011
6 100
7 101
8 110
9 111
1=ON; 0=OFF
If the DIP switch setting is set to (0,0,0), the set temperature will be determined by
the VR3 setting. Otherwise, the setting will override the VR3 setting.
62
63
F) Work Instructions
Conversion of C3 Board from LCD Wireless Control to SLM Wired Control
Step 1 & 2
Step 3
Step 1 : Remove the LED Display hardness wire from the connector CN3;
Step 2 : Connect the SLM handset wire connector to CN3
(Ensure the wire is 10 core wire);
Step 3 : Cut off a capacitor at C6 as highlighted.
Step 4 : Reset the unit.